ME.TRU-18.393…-2
TYPE: ME.TRU-18 18VA CORE SIZE: UI39/13,5
Features - Epoxy resin cast - Two chambers bobbin - Insultation primary-secondary: 4KV. - Increased humidity resistance
Manufacturing standard EN 61558 - Safety insultation transformer - Max.ambient temperature: ta 700C - Insultation class:ta70°/ B 1300C - Double insultated - Degree of protection: IP00 - Not short-circuited
|
Application
-PCB mounting installation
-Low height design
-Possibility of serial and parallel connection of primary and secondary coils
Deviation of secondary voltages 5%
Prescribed primary circuit fuse 125mAT
Modell numer |
Primary Pin voltage configuration |
Secondary Pin voltage configuratuion |
Secondary current |
||
ME.TRU-18.39306-2 |
2×115 V |
1-4 6-9 |
2×6 V |
11-15 16-20 |
2×1,50 A |
ME.TRU-18.39375-2 |
2×115 V |
1-4 6-9 |
2×7,5 V |
11-15 16-20 |
2×1,20 A |
ME.TRU-18.39309-2 |
2×115 V |
1-4 6-9 |
2×9 V |
11-15 16-20 |
2×1,00 A |
ME.TRU-18.39312-2 |
2×115 V |
1-4 6-9 |
2×12 V |
11-15 16-20 |
2×0,75 A |
ME.TRU-18.393135-2 |
2×115 V |
1-4 6-9 |
2×13,5 V |
11-15 16-20 |
2×0,66 A |
ME.TRU-18.39315-2 |
2×115 V |
1-4 6-9 |
2×15 V |
11-15 16-20 |
2×0,60 A |
ME.TRU-18.39318-2 |
2×115 V |
1-4 6-9 |
2×18 V |
11-15 16-20 |
2×0,50 A |
ME.TRU-18.39324-2 * |
2×115 V |
1-4 6-9 |
2×24 V |
11-15 16-20 |
2×0,37 A |
*Certified as
insulation transformer